1. Meter Base Guidlines

(Minimum Requirements for Meter Sockets to be installed at the members premises.)

A. Residential Single Phase

  • Must be U.L. Listed and Labeled
  • Constructed of 12gauge (minimum) steel
  • All edges shall be smooth
  • Enclosures shall be painted a minimum of 2 mil weather-resistant finish
  • Construction in accordance with ANSI/UL50
  • Meter socket jaws must be tin-plated copper
  • Sockets must be 5th terminal adaptable
  • Sockets must be ringless type
  • All sockets rated for greater than 200 amps must be equipped with lever-operated jaw release and bypass
  • All sockets must have a swing style latch or another appropriate latch, which will prevent unauthorized access and accept a 3/8 inch padlock or wire style seal
  • Customer may use a lever-type bypass base

B. Commercial Single Phase

  • Must be U.L. Listed and Labeled
  • Constructed of 12gauge (minimum) steel
  • All edges shall be smooth
  • Enclosures shall be painted a minimum of 2 mil weather-resistant finish
  • Construction in accordance with ANSI/UL50
  • Meter socket jaws must be tin-plated copper
  • Single-phase sockets must be 5th terminal adaptable
  • Sockets must be ringless type
  • Single-phase sockets rated for 200 amps must be equipped with a lever-type meter bypass
  • All single-phase sockets rated for greater than 200 amps must be equipped with lever-operated jaw release and bypass – The bypass must be rated to carry the full load capacity of the socket – These sockets are also required to have the Landis & Gyr HQ series, or the Milbank HD series, or similar block assembly
  • All sockets must have a swing style latch or another appropriate latch, which will prevent unauthorized access and accept a 3/8 inch padlock or wire style seal

C. The following are meter sockets that are acceptable for use

1. 100 Ampere single-phase socket without bypass

  • Milbank – U7487-RL (use for both overhead or underground)
  • T & B Anchor – URS1004B-G-HO
  • Durham – UHT-RS101B
  • Landis & Gyr – UAT111-OG (use for both overhead or underground)
  • Murray – RJ193AX
  • Cutler Hammer – UHT-RS101BCH
  • Square D – UHT-RS101B-SQD

2. 200 Ampere single-phase socket without bypass for overhead service

  • Milbank – U7040-RL (use for overhead or underground)
    U7021 RL KK
  • T & B Anchor – URS1904B-G-HO
  • Durham – UHT-RS203B
  • Landis & Gyr – UAT317-OP
    UAT317-OG
  • Murray – RB198AR
  • Cutler Hammer – UHT-RS203BCH
  • Square D – UHT-RS203B-SQD

3. 200 Ampere single-phase socket without bypass for underground service

  • Milbank – U1980-0
  • T& B Anchor – URS1804B
  • Durham – UHT-RS223A
  • Landis & Gyr – UAS877-PG
    UAT417-OG (use for overhead or underground)
  • Murray – RL199A
  • Cutler Hammer – UHT-RS223ACH
  • Square D – UHT-RS223A-SQD

4. 200 Ampere single-phase socket with bypass

  • Milbank – U9551-RL
    U4216-RXL (lever bypass)
  • T & B Anchor – U42552-HO/HLO
  • Durham – UT-H5213B
  • Landis & Gyr – 40405-02
    40404-025 (use for overhead or underground)
  • Murray – RH173CR
  • Cutler Hammer – UT-H5213BCH
  • Square D – UT-H5213B-SQD

5. 200 Ampere single phase socket, 3 meter position

  • Milbank – U1253-X or S1253-X-CB200
  • Durham – UH-3R2332T
  • Landis & Gyr – 3URS1804BC600
  • Cutler Hammer – UH-3R2332T-CH
  • Square D – UH-3R2332T-SQD

6. 200 Ampere single phase socket, 6 meter position

  • Milbank – U1256-X or S1256-X-CB200
  • Durham – UH-6R2392TT
  • Landis & Gyr – 6URS1804BC600
  • Cutler Hammer – UH-6R2392TT-CH
  • Square D – UH-6R2392TT-SQD

7. Three phase meter bases will be supplied by URE.